High frequency on-line (double conversion VFI type) UPS power grid adaptability test standard
Main standard: GB/T 7260.3-2024 Uninterruptible Power Supply System (UPS) Part 3: Method for Determining Performance and Test Requirements, which is equivalent to adopting IEC 62040-3:2021 China Standard for additional implementation in ... communication scenarios: YD/T 1095-2018 AC Uninterruptible Power Supply (UPS) for communication; EMC anti-interference package: GB/T 7260.2, IEC 61000 series (harmonics, voltage sag, sag, anti-interference) national standard letter. ...
High-frequency on-line UPS belongs to VFI (voltage and frequency independence): the inverter continuously supplies power under normal working conditions, and the output is maintained by the inverter when the power grid is disturbed, which is a typical model for power grid adaptability assessment.
I. Core Test Items and Criteria (GB/T7260.3-2024)
1. Steady-state input voltage adaptability
Examination: UPS can operate stably online without cutting the battery within the range of the manufacturer's nominal input voltage.
Typical range of conventional high-frequency machine: single-phase 176 ~ 264 V (about 20%); Communication class I: 176V~264V, and class II: 187V ~ 242V (YD/T 1095).
Qualified: the output voltage stabilization accuracy meets the nominal (generally ≤ 1% and 2%), and there is no alarm and no protective shutdown.
2. Steady-state input frequency adaptability
Universal: 47 ~ 53Hz (3Hz); Communication yd/t1095: ≥ 48 ~ 52hz.
Qualified: normal rectification work, no automatic battery switching, stable output frequency and normal tracking.
3. Sag/Swell Voltage Sag/Swell
Simulation: voltage drop and sudden rise (typical 30% rated voltage step, sudden change within 20ms, lasting for a specified time)
Decision points (VFI on-line machine): the battery is not switched, the output voltage fluctuates within the tolerance band, and there is no interruption; Output transient deviation and recovery time meet the requirements of product performance grade.
4. Three-phase input imbalance adaptability
Analog three-phase amplitude imbalance, lack of phase (some models support single-phase input)
Qualified: the rectifier continues to work, and the battery is not turned by mistake; Output three-phase voltage unbalance reaches the standard.
5. Power grid harmonic superposition adaptability (distorted power grid)
The 3rd, 5th, 7th and 9th harmonics are superimposed, and THDI operates in 10%/15%/20% multi-gears, with no load, half load and full load.
Qualified: the output voltage THDU is ≤ 3% (linear load), the rectifier is not overcurrent, the device is not protected by mistake, and the temperature rise of the device is normal.
6. Input phase jump (phase mutation)
Input phase step disturbance (typical 30 step)
Qualified: the phase-locked loop is quickly re-locked (generally ≤20ms), and the output waveform has no obvious distortion and disturbance interruption.
7. Short-time interruption (zero voltage interruption)
It can be divided into "interruption time is less than UPS switching time" and exceeding rectification tolerance time: after exceeding tolerance time, it should be reliably converted into battery inverter with uninterrupted load; After the incoming call, it can automatically switch back to the mains mode and recover smoothly.
8. Compound disturbance (voltage+frequency offset at the same time)
Voltage offset and frequency drift are superimposed to simulate the working conditions of generators and weak power grids.
Qualified: stable online operation, no battery cut by mistake and error-free protection.
9. Anti-reverse power transmission (islanding/reverse feed protection)
When the power grid loses power, UPS can't send power reversely to the power grid, which meets the safety requirements of distribution.
Second, distinguish between two concepts
Power grid adaptability (GB/T 7260.3): UPS's ability to withstand power grid disturbance and keep working online (whether it can carry the disturbance without cutting the battery).
EMC immunity (GB/T7260.2/IEC61000-4 series: surge, static electricity, radio frequency field, etc.): immunity to electromagnetic interference, which does not belong to the adaptability of power grid steady state/power quality disturbance, but is often tested synchronously.
Iii. Supplement to Communication Industry (YD/T1095-2018)
Input power factor, input current harmonic limit (THDi)
The frequency tracking rate is 0.5 ~ 2hz/s.
Output voltage imbalance, transient recovery time ≤60ms and other communication special indicators.
Fourth, test equipment
Power network simulator (voltage, frequency, harmonics, sag, phase jump and three-phase imbalance can be set independently), power analyzer, electronic load and oscillograph.