Shenzhen Yunhai Power Technology Co., Ltd. Surge Protector, with good quality and guaranteed safety! Don't worry about choosing
The service life of surge protectors (SPDs) is greatly affected by factors such as working environment, surge impact frequency, installation specifications, etc. The following are specific analysis and reference data:
1、 Theoretical service life
When there is no surge impact
Ideal state: If left in a stable environment without surge impact for a long time, the theoretical lifespan of SPD electronic components (such as varistors and discharge tubes) can reach 10-15 years.
Principle: The aging of varistors is mainly caused by leakage current generated by long-term electrification, and the leakage current increases slowly when there is no impact.
2. Conventional scenarios (with a small amount of impact per year)
Civilian scenarios (such as homes and ordinary office buildings):
It is subject to 5-10 small and medium-sized surge impacts annually, with a typical lifespan of 8-10 years.
Industrial scenarios (such as factories, outdoor equipment):
Due to fluctuations in the power grid or frequent induced lightning strikes, the lifespan is shortened to 5-8 years.
2、 Key factors affecting lifespan
1. Surge impact intensity and frequency
High frequency high current surge:
If located in areas with multiple minefields or close to high-voltage power grids, SPD may experience accelerated degradation of internal components due to frequent operation.
Example: A single 10kA impulse may increase the leakage current of the varistor by 5% -10%, and after multiple attempts, it may exceed the safety threshold, leading to overheating failure.
Critical value reference:
Most SPDs are designed to withstand 50-100 standard shocks (8/20 μ s waveform, In current), and their performance significantly decreases after exceeding this limit.
2. Working environment temperature
High temperature accelerated aging:
SPD is installed in poorly ventilated distribution boxes (such as summer temperatures>40 ℃), and the leakage current of varistors increases exponentially with temperature rise (for every 10 ℃ increase, the leakage current may double), resulting in a 30% -50% reduction in lifespan.
Low temperature impact:
Extreme low temperatures (<-25 ℃) may cause electronic components to become brittle, but their impact on SPD lifespan is smaller than that of high temperatures.
3. Installation and maintenance specifications
Incorrect installation:
Excessive lead length (>1m) or poor grounding can lead to an increase in residual voltage of SPD, indirectly increasing the burden on internal components and potentially shortening their lifespan by 20% -40%.
Lack of maintenance:
Failure to regularly detect leakage current or replace faulty SPDs may result in their inability to operate under critical impacts, and even pose a risk of short circuits.
3、 Typical manifestations of end-of-life
1. Abnormal appearance
Expansion, cracking, or discoloration of the casing (such as yellowing of the casing of a varistor type SPD).
The status indicator light turns red (some products are equipped with a failure indicator).
2. Performance degradation
The leakage current exceeds the maximum value of the product's nominal value (if the leakage current of the varistor SPD is greater than 50 μ A, it needs to be replaced).
The protection level (Up) has significantly increased and cannot meet the equipment's withstand voltage requirements.
3. Abnormal sound or heat
When internal components break down, abnormal noise may be emitted, or the shell temperature may be significantly higher than the ambient temperature (>50 ℃).
4、 Practical suggestions for extending lifespan
1. Graded protection design
Connect SPDs in series between the main distribution box (first level protection) and the front end of the equipment (third level protection) to disperse surge energy and avoid excessive impact on a single level SPD.
Example: The first level SPD bears 80% of the surge energy, while the end level SPD only needs to deal with residual energy, and its lifespan can be extended by more than 50%.
2. Optimize the installation environment
Ensure that the SPD installation location is well ventilated and away from heat sources (such as high-power circuit breakers).
The lead length should be controlled within 0.5m, and short thick wires (such as copper wires with a cross-sectional area ≥ 2.5mm ²) should be used to reduce impedance.
3. Regular testing and maintenance
Civilian scenario: Use a dedicated tester to measure leakage current every year, and check the installation status every 3-5 years.
Industrial scenario: Conduct inspections every six months, increase inspection frequency before thunderstorm season, and record the time and current amplitude of each impact.
4. Choose long-life products
Priority should be given to using a combination of varistors and gas discharge tubes for SPDs, which utilize discharge tubes to withstand high current surges. Varistors are used for precise voltage limiting, reducing the loss of individual components.
Some high-end products, such as the DEHNventil series, use thermal trip technology to prevent overheating, and their lifespan can be extended by 2-3 years compared to ordinary SPDs.
5、 Reference Table for Replacement Cycle
Application scenario: Conventional replacement cycle, multiple lightning zones/high-frequency impact scenarios
Home/office distribution box 8-10 years 5-8 years
Outdoor monitoring equipment 5-8 years 3-5 years
Factory main distribution cabinet 5-7 years 3-4 years
Flammable and explosive places (such as gas stations) 3-5 years 2-3 years
summarize
The lifespan of surge protectors is not a fixed value, and full cycle management needs to be achieved through reasonable design, standardized installation, and regular maintenance. For critical equipment such as data centers and medical instruments, it is recommended to install SPD monitoring modules to track performance parameters in real-time and avoid equipment damage caused by SPD failure. Once any abnormality is found, it should be replaced immediately and should not be used beyond the expiration date.